Note
In the first operating level, the load population recorder is read. The specified parameters are located on the second parameter level. Access to the third parameter level is reserved for ABUS!
Parameter |
Setting range |
Name |
See |
P 0.0 |
0 t – 320 t |
Setting maximum load capacity |
|
P 1.0 |
0 t – 180 t |
Setting maximum load capacity of device's own hoist |
P 1.0/P 2.0/P 3.0 Setting the maximum load capacity of the hoist |
P 2.0 |
0 t – 180 t |
Setting maximum load capacity of hoist at input F2 |
P 1.0/P 2.0/P 3.0 Setting the maximum load capacity of the hoist |
P 3.0 |
0 t – 180 t |
Setting maximum load capacity of hoist at input F3 |
P 1.0/P 2.0/P 3.0 Setting the maximum load capacity of the hoist |
P 4.0 |
0 % – 110 % |
Setting the switching point of the overload protection for the total load of the crane |
P 4.0 Setting the switching point of the overload protection for the total load |
P 4.1 |
0 % – 110 % |
Setting the switching point of the overload protection for device's own hoist |
P 4.1/P 4.2/P 4.3 Setting the switching points of the overload protection of the individual hoists |
P 4.2 |
0 % – 110 % |
Setting the switching point of the overload protection for hoist at input F2 |
P 4.1/P 4.2/P 4.3 Setting the switching points of the overload protection of the individual hoists |
P 4.3 |
0 % – 110 % |
Setting the switching point of the overload protection for hoist at input F3 |
P 4.1/P 4.2/P 4.3 Setting the switching points of the overload protection of the individual hoists |
P 4.40 |
0 % – 110 % |
Setting the second load-controlled switching point for the total load of the crane |
P 4.40 Setting the second load-controlled switching point for the total load |
P 4.41 |
0 % – 110 % |
Setting the second load-controlled switching point for device's own hoist |
P 4.41/P 4.42/P 4.43 Setting the second load-controlled switching point of the hoists |
P 4.42 |
0 % – 110 % |
Setting the second load-controlled switching point for the hoist at input F2 |
P 4.41/P 4.42/P 4.43 Setting the second load-controlled switching point of the hoists |
P 4.43 |
0 % – 110 % |
Setting the second load-controlled switching point for the hoist at input F3 |
P 4.41/P 4.42/P 4.43 Setting the second load-controlled switching point of the hoists |
P 4.5 |
0 % – 110 % |
Setting the load-controlled switching point on the current transformer module |
|
P 5.0 |
|
Without function |
|
P 5.01 |
|
Setting the “rapid load increase” sensitivity |
|
P 5.1 |
In h |
Showing the theoretical service life |
|
P 5.2 |
In h |
Reading the load population recorder |
|
P 5.3 |
|
Test at the inspection before initial commissioning |
|
P 5.4 |
|
Performing device diagnosis |
|
P 5.5 |
|
Deleting values |
|
P 5.6 |
1 – 9999 |
Setting the current correction factor |
|
P 5.7 |
0, 1, 2 |
Setting the operation on a twin hoist |
|
P 5.8 |
0, 1 |
Enabling operation with ABUS synchronization control system |
P 5.8 Enabling operation with ABUS synchronization control system |
P 5.10 |
P 5.11 – P 5.99 |
Enabling operation with ABULiner frequency
converter |
|
P 9.9 |
|
Exiting the parameter level |
Parameter |
Setting range |
Name |
See |
P 1.1 |
In kHz |
Performing a zero point adjustment for device's own hoist |
|
P 1.2 |
|
Setting with test load for device's own hoist |
|
P 1.3 |
0 Hz – 64999 kHz |
Reading or entering the zero point frequency for device's own hoist |
P 1.3/P 2.3/P 3.3 Reading or entering the zero point frequency |
P 1.4 |
0 Hz – 64999 |
Reading or entering the gain factor for device's own hoist |
|
P 2.1 |
In kHz |
Performing a zero point adjustment for hoist at input F2 |
|
P 2.2 |
|
Setting with test load for hoist at input F2 |
|
P 2.3 |
0 Hz – 64999 kHz |
Reading or entering the zero point frequency for hoist at input F2 |
P 1.3/P 2.3/P 3.3 Reading or entering the zero point frequency |
P 2.4 |
0 Hz – 64999 |
Reading or entering the gain factor for hoist at input F2 |
|
P 3.1 |
In kHz |
Performing a zero point adjustment for hoist at input F3 |
|
P 3.2 |
|
Setting with test load for hoist at input F3 |
|
P 3.3 |
0 Hz – 64999 kHz |
Reading or entering the zero point frequency for hoist at input F3 |
P 1.3/P 2.3/P 3.3 Reading or entering the zero point frequency |
P 3.4 |
0 Hz – 64999 |
Reading or entering the gain factor for hoist at input F3 |
|
P 6.1 |
10 h – 124000 h |
Entering the theoretical service life |
|
P 6.2 |
0 h – 124000 h |
Entering starting value |
|
P 6.3 |
|
Deleting values (including load population recorder) |
|
P 6.4 |
0 h – 21845 h |
Showing actual hours of use S |
|
P 6.5 |
0 h – 65535 h |
Showing operating hours Ti |
|
P 7.00 |
0 t – 408 t |
Showing load display of total load |
|
P 7.01 |
0 t – 127 t |
Showing load display of device's own hoist |
|
P 7.02 |
0 t – 127 t |
Showing load display of hoist at input F2 |
|
P 7.03 |
0 t – 127 t |
Showing load display of hoist at input F3 |
|
P 7.1 |
0 Hz – 65535 kHz |
Showing measurement frequency of device's own hoist |
|
P 7.2 |
0 Hz – 65535 kHz |
Showing measurement frequency at input F2 |
|
P 7.3 |
0 Hz – 65535 kHz |
Showing measurement frequency at input F3 |
|
P 7.4 |
|
Without function |
|
P 7.5 |
0 A – 185 A |
Showing motor current |
|
P 7.6 |
0 V – 627 V |
Showing mains voltage |
|
P 7.61 |
In V |
Mains voltage analysis |
|
P 7.7 |
0 Hz – 120 Hz |
Showing motor frequency |
|
P 8.0 |
|
Password for parameter level 3 |
|
P 9.9 |
|
Exiting the parameter level |