P 4.41/P 4.42/P 4.43 Setting the second load-controlled switching point of the hoists

In this parameter you can set the second load-controlled switching points of the individual hoists. The parameters always refer to the device's own hoist, meaning the hoist on which the device just set is installed (connected at input F1) and up to two additional hoists at input F2 and F3. The value lies between 0% and 110% of the maximum load capacity of the hoist and can be set in 2% steps.

The corresponding hoist at the respective input switches off after the saved value is exceeded, and the overload protection goes into overload status. At the same time, the LIS-SV displays the load and flashes once per second.

The second load-controlled switching point of the overload protection is activated through the switching of input EA on the LIS-SV. This enables switching of e.g. a signal lamp that lights up in the event of an overload.

The set value always refers to the setting of the maximum load capacity in P 1.0 for input F1, P 2.0 for input F2 or P 3.0 for input F3.

 

*   Select the corresponding parameters with the arrow buttons.

─     P 4.41 for device's own load signal (input F1)

─     P 4.42 for the load signal at input F2

─     P 4.43 for the load signal at input F3

*   Press Enter briefly.

●   The parameter is opened.

*   Set the value between 0% and 110% of the load capacity of the respective hoist.

*   Press Enter briefly.

●   The value is saved.