The corresponding hoist at the respective input switches off after the saved value is exceeded, and the overload protection goes into overload status. At the same time, the LIS-SV displays the load and flashes once per second.
The second load-controlled switching point of the overload protection is activated through the switching of input EA on the LIS-SV. This enables switching of e.g. a signal lamp that lights up in the event of an overload.
The set value always refers to the setting of the maximum load capacity in P 1.0 for input F1, P 2.0 for input F2 or P 3.0 for input F3.
Select the corresponding
parameters with the arrow buttons.
─ P 4.41 for device's own load signal (input F1)
─ P 4.42 for the load signal at input F2
─ P 4.43 for the load signal at input F3
Press Enter briefly.
● The parameter is opened.
Set the value between 0% and
110% of the load capacity of the respective hoist.
Press Enter briefly.
● The value is saved.