P 1.4/P 2.4/P 3.4 Reading or entering the gain factor

With these parameters you can read or enter the value of the gain factor for the respective hoist. The gain factor is the angle of the load lines from which the LIS-SV calculates the weight of the suspended load using the zero point frequency and the measurement frequency. These parameters are also used to set the slope of the load lines.

 

Note

Entering or changing a known measured value is only necessary when a device is exchanged. In this case, known measured values from an old device can be transferred to the new device, or measured values from another hoist can be entered. Otherwise the value is not to be changed!

 

Warnung stürzende Last

Danger from load drop due to overload!

Changing the gain factor leads to overload of the crane.

If a value deviating from the measured value in “Setting with test load” is entered, this will lead to an overload of the crane. This in turn means the raised load could fall and kill or injure people!

Do not enter any value that deviates from the measured value!

 

 

*   Select the corresponding parameters with the arrow buttons.

─     P 1.4 for device's own load signal (input F1)

─     P 2.4 for the load signal at input F2

─     P 3.4 for the load signal at input F3

*   Press Enter briefly.

●   The current saved value is displayed.

*   Hold Enter pressed until “Code” appears in the display.

*   Hold Enter pressed.

*   Enter code 1443.

*   Press Enter briefly.

*   Enter the measured or read out value.

*   Press Enter briefly.

●   The entered value is saved.