With these parameters you can read or enter the value of the frequency [in kHz] in the zero point for the respective hoist. The value lies between 0.5 kHz and 1 kHz so that in the event of a broken wire the value can drop to “0” and the LIS-SV will detect the missing signal.
Select the corresponding
parameters with the arrow buttons.
─ P 1.3 for device's own load signal (input F1)
─ P 2.3 for the load signal at input F2
─ P 3.3 for the load signal at input F3
Press Enter briefly.
● The current saved value is displayed.
Hold Enter pressed until “Code”
appears in the display.
Hold Enter pressed.
Enter code 1443.
Press Enter briefly.
Enter a value from 0.5 kHz
to 1 kHz.
Press Enter briefly.
● The entered value is saved.