Note
During the measurement, no test load or lifting tackle is allowed to hang from the hook.
Select the corresponding
parameters with the arrow buttons:
─ P 1.1 for device's own load signal (input F1)
─ P 2.1 for the load signal at input F2
─ P 3.1 for the load signal at input F3
|
|
|
|
|
|
Hold Enter pressed until “Code”
appears in the display.
Hold Enter pressed.
Enter code 1443.
|
|
|
|
|
|
Press Enter briefly.
● After pressing Enter, “MESS” appears on the display.
● After 2 s the value of the measured frequency with empty load hook appears on the display.
Hold Enter pressed until the
corresponding parameter (P 1.1/P 2.1/P 3.1) appears.
The respective parameter can only be exited if the measured frequency value is greater than 0.100 kHz.
● The measured value is saved.