P 4.1/P 4.2/P 4.3 Setting the switching points of the overload protection of the individual hoists

In these parameters you can set the switching points of the overload protection of the individual hoists. The parameters always refer to the device's own hoist, meaning the hoist on which the device just set is installed (connected at input F1) and up to two additional hoists at input F2 and F3. The value lies between 0% and 110% of the maximum load capacity and can be set in 2% steps.

The corresponding hoist at the respective input switches off after the saved value is exceeded, and the overload protection goes into overload status. At the same time, the LIS-SV displays the load and flashes once per second.

 

*   Select the corresponding parameters with the arrow buttons:

─     P 4.1 for device's own load signal (input F1)

─     P 4.2 for the load signal at input F2

─     P 4.3 for the load signal at input F3

*   Press Enter briefly.

●   The parameter is opened.

*   Set the value between 2% and 110% of the maximum load capacity of the respective hoist.

*   Press Enter briefly.

●   The value is saved.