In this parameter you set the sensitivity of the hoist response to lifting with a sudden jolt. When lifting with a sudden jolt occurs, the hoist switches from fast lifting back to slow lifting speed until the rapid load increase is over.
The value has no unit of measurement and can be set between 20 and 255. In this range, 20 is very sensitive and 255 is the lowest sensitivity.
Note
The parameter can only be accessed with a special code! Whenever adjustment of the rapid load increase is necessary, contact your ABUS Service representative. See ABUS Service.
Select parameter P 5.01 with the
arrow buttons.
Press Enter briefly.
● The parameter is opened.
● The current value is displayed.
Hold Enter pressed until “Code” appears in the display.
Hold Enter pressed.
Enter code.
Press Enter briefly.
Input the value with the arrow buttons.
Press Enter briefly.
● The value is saved.