This parameter is used to manually switch the relays of the LIS-SE. The control signal can also be checked at the inputs E1 to E7 and EA.
The parameter is divided into 3 areas:
─ Test of the relays for the outputs
─ Test of the second load-controlled switching point
─ Test of the inputs E1 – E7, EA
The hoist does not lift and lower if this parameter is active!
Select parameter P 2.4 with
the arrow buttons.
● “Code” is displayed.
Hold Enter pressed.
Enter code 1443.
Press Enter briefly.
● The parameter is opened.
Call up the next switching
points in the table one after another by pressing Enter.
The different switching points in the table allow the relays for the outputs and inputs to be checked. Checking the second load-controlled switching point is not yet possible.
Test of the relays for the outputs | |||||||
|
Status of the switching contacts |
Display |
Remark |
Error case display | |||
Test point |
Lift |
Lower |
Fast |
Monitoring |
|
|
|
- - 0 - |
0 |
0 |
0 |
0 |
0001 |
All relays in standby |
0000 |
- - 1 - |
1 |
0 |
0 |
0 |
1000 |
Relay for “Lift” switched |
1001 |
- - 2 - |
0 |
1 |
0 |
0 |
0100 |
Relay for “Lower” switched |
0101 |
- - 3 - |
0 |
0 |
1 |
1 |
0011 |
Relay for “Fast” switched |
0010 |
Test of the second load-controlled switching point | |
- - 4 - |
Test for the second load-controlled switching point: not currently active! |
- - 5 - |
Test of the inputs E6/E2/E7/EA | |||||||
|
Status of the inputs |
Display |
Remark |
Error case display | |||
Test point |
E6 |
E2 |
E7 |
EA |
|
|
|
- - 6 - |
0 |
0 |
0 |
0 |
4000 |
No signal at the inputs Monitoring OK |
0000 |
1 |
0 |
0 |
0 |
0001 |
Signal at input for “Lift” |
4000 | |
0 |
1 |
0 |
0 |
0020 |
Signal at input for “Lower” |
4000 | |
1 |
0 |
1 |
1 |
0301 |
Signal at input for “Fast/Lift” |
4000 | |
0 |
1 |
1 |
1 |
0320 |
Signal at input for “Fast/Lower” |
4000 |
Test of the inputs E5/E4/E3/E1 | |||||||
|
Status of the inputs |
Display |
Remark |
Error case display | |||
Test point |
E5 |
E4 |
E3 |
E1 |
|
|
|
- - 7 - |
|
|
|
|
|
Input E1 not active! |
|
|
|
|
|
|
Input E3 not active! |
| |
0 |
1 |
0 |
0 |
0700 |
Signal at input E4 evaluated (optional – only with two trolleys in joint operation) |
0000 | |
1 |
0 |
0 |
0 |
8000 |
Signal at input E5 evaluated (optional – only with two trolleys in joint operation) |
0000 |