P 2.4 Device diagnosis

This parameter is used to manually switch the relays of the LIS-SE. The control signal can also be checked at the inputs E1 to E7 and EA.

 

Note

The parameter is divided into 3 areas:

─     Test of the relays for the outputs

─     Test of the second load-controlled switching point

─     Test of the inputs E1 – E7, EA

 

The hoist does not lift and lower if this parameter is active!

*   Select parameter P 2.4 with the arrow buttons.

*   Press Enter briefly.

●   “Code” is displayed.

*   Hold Enter pressed.

*   Enter code 1443.

*   Press Enter briefly.

●   The parameter is opened.

*   Call up the next switching points in the table one after another by pressing Enter.

The different switching points in the table allow the relays for the outputs and inputs to be checked. Checking the second load-controlled switching point is not yet possible.

 

 

 

 

Test of the relays for the outputs

 

Status of the switching contacts

Display

Remark

Error case display

Test point

Lift

Lower

Fast

Monitoring

 

 

 

- - 0 -

0

0

0

0

0001

All relays in standby

0000

- - 1 -

1

0

0

0

1000

Relay for “Lift” switched

1001

- - 2 -

0

1

0

0

0100

Relay for “Lower” switched

0101

- - 3 -

0

0

1

1

0011

Relay for “Fast” switched

0010

 

Test of the second load-controlled switching point

- - 4 -

Test for the second load-controlled switching point: not currently active!

- - 5 -

 

Test of the inputs E6/E2/E7/EA

 

Status of the inputs

Display

Remark

Error case display

Test point

E6

E2

E7

EA

 

 

 

- - 6 -

0

0

0

0

4000

No signal at the inputs

Monitoring OK

0000

1

0

0

0

0001

Signal at input for “Lift”

4000

0

1

0

0

0020

Signal at input for “Lower”

4000

1

0

1

1

0301

Signal at input for “Fast/Lift”

4000

0

1

1

1

0320

Signal at input for “Fast/Lower”

4000

 

Test of the inputs E5/E4/E3/E1

 

Status of the inputs

Display

Remark

Error case display

Test point

E5

E4

E3

E1

 

 

 

- - 7 -

 

 

 

 

 

Input E1 not active!

 

 

 

 

 

 

Input E3 not active!

 

0

1

0

0

0700

Signal at input E4 evaluated (optional – only with two trolleys in joint operation)

0000

1

0

0

0

8000

Signal at input E5 evaluated (optional – only with two trolleys in joint operation)

0000