If the hoist limit switch is incorrectly set or during a technical fault, it can happen that the backup limiter is nevertheless activated. Then the backup limiter must be bridged so that the crane can be switched on again.
|
Adjacent jumper |
|
|
| |
|
|
Prong terminal block -X31 |
Remove the adjacent jumper
between terminal 2 and 3 on the prong terminal block -X31.
Insert the removed adjacent
jumper between terminal 2 and 1 on the prong terminal block -X31.
Press the emergency stop and
unlock again.
● The fault message is thus activated on ABUControl.
Wait until the frequency
converter has started.
Lower the load hook until the
backup limiter switching point is no longer activated.
The load hook can only be lowered.
Put the adjacent jumper from
terminal 2 and 1 on terminal 2 and 3 back on the prong terminal block -X31.
If necessary: Reset backup
limiter and the top hoist limiter.